Field Setting Si30-813
136 Test Operation
f Set Cool / Heat for More Than One Outside Unit System Simultaneously in Accordance with Unified
Master Outside Unit by Cool/Heat Switching Remote Controller
Add and change the following items to
e
.
Install cool/heat switching remote controller on the group master outside unit.
Set SS1 on the group master outside unit PC board.
Supplementation on e and f.
When switching cool/heat for each adaptor PC board with the use of more than one adaptor PC
board, set the address of the adaptor PC board DS1 and DS2 so that it matches the unified
cool/heat address of outside unit PC board.