Si30-813 Field Setting
Test Operation 149
Emergency operation with settings in service mode
“Inhibition of operation” is set with each outside unit.
Make the following settings with the master unit. (Setting with the slave unit becomes disabled.)
Discriminate the operating status of the master unit/slave units through the following LED
display.
• To inhibit the master unit from operating
Set
setting mode 2 from No. 38 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 38 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
• To inhibit the slave unit 1 from operating
Set
setting mode 2 from No. 39 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 39 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
• To inhibit the slave unit 2 from operating
Set
setting mode 2 from No. 40 to No. 2.
(Procedure)
(1) Press and hold the MODE button (BS1) for 5 sec. or
more.
(2) Press the SET button (BS2) 40 times.
(3) Press the RETURN button (BS3) once.
(4) Press the SET button (BS2) once.
(5) Press the RETURN button (BS3) twice.
(6) Press the MODE button (BS1) once.
• In the case of multi-outside-unit system, when the
above “Inhibition of operation” is set, outside unit rotation is not functional.
LED display (
k
:ON
h
h
:OFF
l
l
:Blink)
H1P
---
H7P H8P
(Factory set)
Master:
Slave 1:
Slave 2:
LED display (
k
:ON
h
h
:OFF
l
l
:Blink)
H1P
---
H7P
(Factory set)
LED display (
k
:ON
h
h
:OFF
l
l
:Blink)
H1P
---
H7P
(Factory set)
LED display (
k
:ON
h
h
:OFF
l
l
:Blink)
H1P
---
H7P
(Factory set)
Notes : Reset the power supply during the outside unit is stopping to cancel the
automatic backup operation forcibly.