Daikin RWEYQ28PY1 [31/342] Bs units

Daikin RWEYQ30PY1 [31/342] Bs units
Specifications Si30-813
20 Specifications
1.3 BS Units
Notes:
1 When connecting with a 20 to 50 class indoor unit, connect to the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
2 When connecting with an indoor unit of 150 or more and 160 or less, connect to the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
3 When connecting with a 200 class, or more than 160 and less than 200 class indoor unit, connect to the attached pipe to the field pipe.
(Braze the connection between the attached and field pipe.)
Notes:
1 In case of connecting with a 07~18 type indoor unit, match to the size of field pipe using the attached pipe.
(Connection between the attached pipe and the field pipe must be brazed.)
2 In case of connecting with indoor unit capacity index 54 or more and 60 or less, match to the size of the field pipe using the attached
pipe.
(Connection between the attached pipe and the field pipe must be brazed.)
Model BSVQ100PV1 BSVQ160PV1 BSVQ250PV1
Power Supply 1 Phase 50Hz 200-240V 1 Phase 50Hz 200-240V 1 Phase 50Hz 200-240V
Total Capacity Index of Indoor Unit 20 to 100 More than 100 but 160 or less More than 160 but 250 or less
No. of Connectable Indoor Units Max. 5 Max. 8 Max. 8
Casing Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 207×388×326 207×388×326 207×388×326
Sound Absorbing Thermal Insulation
Material
Foamed polyurethane, Flame resistant
needle felt
Foamed polyurethane, Flame resistant
needle felt
Foamed polyurethane, Flame resistant
needle felt
Piping
Connection
Indoor
Unit
Liquid Pipes 9.5mm C1220T (brazing connection)
1 9.5mm C1220T (brazing connection) 9.5mm C1220T (brazing connection)
Gas Pipes
15.9mm C1220T (brazing connection)
1 15.9mm C1220T (brazing connection)
2 22.2mm C1220T (brazing connection)
3
Outdoor
Unit
Liquid Pipes 9.5mm C1220T (brazing connection) 9.5mm C1220T (brazing connection) 9.5mm C1220T (brazing connection)
Suction Gas Pipes
15.9mm C1220T (brazing connection) 15.9mm C1220T (brazing connection)
2 22.2mm C1220T (brazing connection)
3
HP/LP Gas Pipes
12.7mm C1220T (brazing connection) 12.7mm C1220T (brazing connection)
2 19.1mm C1220T (brazing connection)
3
Weight kg 14 14 15
Standard Accessories
Installation manual, Attached pipe
Insulation pipe cover, Clamps
Installation manual, Attached pipe
Insulation pipe cover, Clamps
Installation manual, Attached pipe
Insulation pipe cover, Clamps
Drawing No. C: 4D057926 C: 4D057927 C: 4D057928
Model BSVQ36PVJU BSVQ60PVJU
Power Supply 1 Phase 60Hz 208~230V 1 Phase 60Hz 208~230V
Total Capacity Index of Connectable Indoor
Unit
Less than 36 Less than 60
No. of Connectable Indoor Units Max. 5 Max. 8
Casing Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) in 8-1/8 × 15-1/4 × 12-13/16 8-1/8 × 15-1/4 × 12-13/16
Sound Absorbing Thermal Insulation
Material
Foamed Polyurethane, Frame Resisting Needle Felt Foamed Polyurethane, Frame Resisting Needle Felt
Piping
Connection
Indoor
Unit
Liquid Pipes
φ
3/8 C1220T (Brazing Connection)
1
φ
3/8 C1220T (Brazing Connection)
Gas Pipes
φ
5/8 C1220T (Brazing Connection)
1
φ
5/8 C1220T (Brazing Connection)
2
Outdoor
Unit
Liquid Pipes
φ
3/8 C1220T (Brazing Connection)
φ
3/8 C1220T (Brazing Connection)
Suction Gas Pipes
φ
5/8 C1220T (Brazing Connection)
φ
5/8 C1220T (Brazing Connection)
2
Discharge Gas
Pipes
φ
1/2 C1220T (Brazing Connection)
φ
1/2 C1220T (Brazing Connection)
2
Mass Lbs 26 26
Standard Accessories
Installation Manual, Attached Pipe, Insulation Pipe Cover,
Clamps
Installation Manual, Attached Pipe, Insulation Pipe Cover,
Clamps
Drawing No. 4D058233A 4D058234A