Daikin RWEYQ28PY1 [246/342] Malfunction of transmission between indoor and outside units in the same system

Daikin RWEYQ30PY1 [246/342] Malfunction of transmission between indoor and outside units in the same system
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 235
2.47
U9
Malfunction of Transmission between Indoor and
Outside Units in the Same System
Remote
Controller
Display
U9
Applicable
Models
Indoor unit
FXFQ, FXCQ, FXKQ, FXDQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ, FXUQ
Method of
Malfunction
Detection
Detect the malfunction signal of any other indoor unit within the system concerned.
Malfunction
Decision
Conditions
When the malfunction decision is made on any other indoor unit within the system concerned.
Supposed
Causes
Malfunction of transmission within or outside of other system
Malfunction of electronic expansion valve in indoor unit of other system
Defect of PC board of indoor unit in other system
Improper connection of transmission wiring between indoor and outside unit