Daikin RWEYQ28PY1 [234/342] Low pressure drop due to refrigerant shortage or electronic expansion valve failure

Daikin RWEYQ28PY1 [234/342] Low pressure drop due to refrigerant shortage or electronic expansion valve failure
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 223
2.39
U0
Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure
Remote
Controller
Display
U0
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Detect insufficient gas using low pressure or difference in temperature between the suction pipe
and the heat exchanger.
Malfunction
Decision
Conditions
In cooling
Low pressure of 0.25 MPa or less continues for 30 minutes
In heating
Suction gas superheated degree of 20°C or more continues for 60 minutes.
Abnormality is not confirmed and operation is continued.
Supposed
Causes
Insufficient gas or clogged refrigerant (wrong piping)
Faulty thermistor (R2T, R4T)
Faulty low pressure sensor
Faulty main PC board (A1P)