Daikin RWEYQ28PY1 [279/342] Procedure for mounting dismounting of switch box

Daikin RWEYQ30PY1 [279/342] Procedure for mounting dismounting of switch box
Procedure for Mounting / Dismounting of Switch Box Si30-813
268 Procedure for Mounting / Dismounting of Switch Box
1. Procedure for Mounting / Dismounting of Switch
Box
1.1 Procedure for Dismounting
1. Dismount the lid from the switch box.
2. Disconnect high voltage and low voltage wirings from the PC board and the terminal blocks,
referring to Figure on the right.
3. Unscrew mounting screws from the top plate, the stop valve mounting plate, and the bottom
frame in a total of 6 places.
4. With attention paid not to make the switch box support leg into contact with the side panel,
rotate the switch box to pull out it, while referring to Figure on the right.
In order to pull out the switch box, check to be sure no wirings get stuck with the switch box.
Procedure for Mounting/Dismounting of Switch Box
1.2 Procedure for Mounting
Mount the switch box, following the procedure for dismounting in reverse.
After the completion of mounting, check to be sure connectors are all properly connected.