Daikin RWEYQ28PY1 [228/342] Outside unit inverter current abnormal

Daikin RWEYQ30PY1 [228/342] Outside unit inverter current abnormal
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 217
2.34
L8
Outside Unit: Inverter Current Abnormal
Remote
Controller
Display
L8
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Malfunction is detected by current flowing in the power transistor.
Malfunction
Decision
Conditions
When overload in the compressor is detected.
Supposed
Causes
Compressor overload
Compressor coil disconnected
Defect of inverter PC board
Troubleshooting Output current check
Higher voltage than actual is displayed when the inverter output voltage is checked by tester.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Inverter
output voltage
check Inverter output
voltage is not balanced.
(Normal if within ±10V for Y1,
YL power supply and ±5V for TL
power supply ) Must be
measured when
frequency
is stable.
Compressor overload
Inspection of the compressor and
refrigerant system is required.
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
NO
Replace the inverter PC board.
YES
NO
Reset and restart.
NO
The
secondary
current of the inverter is
higher than 16.5A (Y1, YL power
supply) and 25.1 A (TL
power supply) for
each phase.
Replace the compressor.
NO
YES
Compressor
inspection The
compressor's coil is
disconnected.
YES
YES
Disconnect the the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
After turning
on again, "
L8" blinks
again.