Daikin RWEYQ28PY1 [215/342] Refrigerant overcharged

Daikin RWEYQ30PY1 [215/342] Refrigerant overcharged
Troubleshooting by Indication on the Remote Controller Si30-813
204 Troubleshooting
2.23
F6
Refrigerant Overcharged
Remote
Controller
Display
F6
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Detect excessive charging of refrigerant using suction pipe temperature and subcooling heat
exchanger outlet temperature during check operation.
Malfunction
Decision
Conditions
When the suction pipe temperature and the subcooling heat exchanger outlet temperature
during check operation drop and become below the evaporation temperature
Supposed
Causes
Excessive refrigerant charging
Suction pipe thermistor removed
Subcooling heat exchanger outlet thermistor removed