Daikin RWEYQ28PY1 [213/342] Normal

Daikin RWEYQ30PY1 [213/342] Normal
Troubleshooting by Indication on the Remote Controller Si30-813
202 Troubleshooting
1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
{
: Continuity
× : No continuity
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown
1. White × {
Approx.
300
× {
Approx.
150
×
2. Yellow × {
Approx.
300
× {
Approx.
150
3. Orange × {
Approx.
150
×
4. Blue × {
Approx.
150
5. Red ×
6. Brown
M
White (1)
Yellow
(2)
Blue
(4)
Brown
(6)
Red (5)
Orange (3)
φ1
φ2 φ4
φ3
(1) White
(2) Yellow
(3) Orange
(4) Blue
(5) Red
(6) Brown
X26A or
X28A

Содержание

Скачать