Daikin RWEYQ28PY1 [266/342] Troubleshooting op unified on off controller

Daikin RWEYQ28PY1 [266/342] Troubleshooting op unified on off controller
Si30-813 Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 255
5. Troubleshooting (OP: Unified ON/OFF Controller)
5.1 Operation Lamp Blinks
Remote
Controller
Display
Operation lamp blinks
Applicable
Models
Indoor unit
FXFQ, FXCQ, FXKQ, FXDQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ, FXUQ
Unified ON/OFF controller
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
Supposed
Causes
Malfunction of transmission between optional controller and indoor unit
Connector for setting master controller is disconnected
Defect of unified ON/OFF controller
Defect of indoor unit PC board
Malfunction of air conditioner