Daikin RWEYQ28PY1 [89/342] In heating or cooling heating simultaneous operation when the outside unit heat exchanger is used as condenser

Daikin RWEYQ30PY1 [89/342] In heating or cooling heating simultaneous operation when the outside unit heat exchanger is used as condenser
Protection Control Si30-813
78 Function
[In heating or cooling/heating simultaneous operation] (When the outside unit heat
exchanger is used as condenser.)
Low pressure standby
Normal operation
Pc < 0.44 MPa
Comp. upper limit down 3 steps/10 sec.
Compressor 52 Hz
Compressor upper limit
frequency = 216Hz
Pe < 0.07 MPa
When occurring 4 times within 60 min.,
the malfunction code “E4” is output.
1 Pe: LP pressure sensor detection
value for each outside unit.
2 This frequency control is carried
out in each outside unit.
Less than 3 times
within 60 min.
Pe > 0.49 MPa
Pe < 0.34 MPa
Comp. upper limit up 1 step/20 sec.
Pe < 0.44 MPa