Daikin RWEYQ28PY1 [92/342] Cooling fan control

Daikin RWEYQ30PY1 [92/342] Cooling fan control
Si30-813 Protection Control
Function 81
6.5 Cooling Fan Control
his function is used for ON-OFF control of the cooling fan to cool the inverter. This cooling fan
operates only when the temperature of the inverter fan is high, in order to reduce the operating
time of the fan.
[Details]
Control the cooling fan by each outside unit.
Cooling fan OFF Cooling fan ON
· 52C1=ON
· T fin > 50˚C
&
· 52C1=OFF
· T fin < 30˚C
OR

Содержание