Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 199
2.20
E5
Compressor Motor Lock
Remote
Controller
Display
E5
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Pick up the location signal using the inverter PC board from the UVWN line connected between
the inverter and the compressor and detect location signal pattern.
Malfunction
Decision
Conditions
In normal operation, location signal for a triple cycle of frequency applied, while in locked
operation, it is a double cycle, and they are detected.
(Retry twice/60 minutes)
Supposed
Causes
Inverter compressor lock
High differential pressure (0.5 MPa or more)
Incorrect UVWN wire connection
Faulty inverter PC board
Stop valve left closed