Daikin RWEYQ28PY1 [239/342] Check operation not executed

Daikin RWEYQ30PY1 [239/342] Check operation not executed
Troubleshooting by Indication on the Remote Controller Si30-813
228 Troubleshooting
2.42
U3
Check Operation not Executed
Remote
Controller
Display
U3
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Check operation is executed or not
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
Check operation is not executed.
Troubleshooting
Has the
check operation
performed on Outside
unit PC board?
Press the BS4 on PC board on the
master outside unit for 5 seconds
or more to execute check
operation.
Replace the main PC board on the
outside unit.
NO
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.