Daikin RWEYQ28PY1 [184/342] Abnormal indoor fan motor

Daikin RWEYQ10PY1 [184/342] Abnormal indoor fan motor
Si30-813 Troubleshooting by Indication on the Remote Controller
Troubleshooting 173
A6
Abnormal Indoor Fan Motor
Remote
Controller
Display
A6
Applicable
Models
Indoor unit
FXFQ, FXAQ
Method of
Malfunction
Detection
Detect abnormal fan rotation with the signal from the fan motor
Malfunction
Decision
Conditions
When fan rotation does not increase
Supposed
Causes
Disconnected/short-circuited fan motor harnesses or disconnected connectors
Faulty fan motor
(Disconnection and insulation failure)
Abnormal signal from the fan motor
(Circuit breakdown)
Faulty PC board
Instantaneous disturbance of power supply voltage
Fan motor lock
(Caused by the motor or external factors)
Fan does not rotate because foreign particles are trapped in it.
Disconnected connector between PC board A1P and A2P