Daikin RWEYQ28PY1 [15/342] Design flexibility

Daikin RWEYQ30PY1 [15/342] Design flexibility
Features Si30-813
4 General Information
1.1 Design Flexibility
Enhanced design flexibility and cold climate capability
Indoor installation
The system can tolerate water pressure up to 1.96 MPa.
VRV-WIII
Cooling tower (Closed type)
Indoor installation
VRV-WIII
Water cooled VRV III uses water as its heat source, so it is optimal for large buildings, including tall,
multi-storey buildings, because the system can tolerate water pressure of up to 1.96 MPa.
Furthermore, if the currently installed heat source’s water temperature is between 10˚C and 45˚C, it
may be possible to use the existing water pipe work and heat source. This alone makes it an ideal
system solution for building refurbishment projects. Because the system is water cooled, outdoor air
temperature does not affect its heating capacity. In addition, water cooling means no defrost
operation is required, and the resultant rapid start-up time assures quick and comfortable heating,
even in cold environments.