Daikin RWEYQ28PY1 [217/342] Malfunction of water system

Daikin RWEYQ30PY1 [217/342] Malfunction of water system
Troubleshooting by Indication on the Remote Controller Si30-813
206 Troubleshooting
2.24
HJ
Malfunction of Water System
Remote
Controller
Display
HJ
Applicable
Models
Outside unit
RWEYQ8P, 10P
Method of
Malfunction
Detection
Detect abnormalities using the thermistor on the side of the heat exchanger gas.
Detect turned off interlock circuit.
(When interlock setting is provided.)
Malfunction
Decision
Conditions
When temperature on the heat exchanger gas side (R4T) drops remarkably with the
smallest operation step (52 Hz) of the compressor
With interlock setting provided, when interlock circuit is turned off.
Supposed
Causes
Clogged water piping system
Insufficient heat exchanger water
Dirty heat exchanger
Disconnected connector
Faulty thermistor on the heat exchanger gas side
Faulty low pressure sensor