Si30-813 Troubleshooting by Remote Controller
Troubleshooting 163
Malfunction
code
Operation
lamp
Malfunction contents
Page
Referred
Indoor Unit A0 l Error of external protection device 168
A1 l PC board defect, E
2
PROM defect 169
A3 l Malfunction of drain level control system (S1L) 170
A6 l Fan motor (M1F) lock, overload
Abnormal indoor fan motor
172
173
A7 k Malfunction of swing flap motor (MA) 179
A8 l Abnormal power supply voltage 181
A9 l Malfunction of moving part of electronic expansion valve (20E) 182
AF k Drain level above limit 184
AH k Malfunction of air filter maintenance
AJ l Malfunction of capacity determination device 185
C1 l Failure of transmission (between indoor unit PC board and fan PC
board)
186
C4 l Malfunction of thermistor (R2T) for heat exchanger (loose
connection, disconnection, short circuit, failure)
188
C5 l Malfunction of thermistor (R3T) for gas pipes (loose connection,
disconnection, short circuit, failure)
189
C6 l Failure of combination (between indoor unit PC board and fan PC
board)
190
C9 l Malfunction of thermistor (R1T) for suction air (loose connection,
disconnection, short circuit, failure)
191
CC k Malfunction of humidity sensor system 192
CJ k Malfunction of thermostat sensor in remote controller 193
Outside Unit E1 l PC board defect 194
E3 l Actuation of high pressure switch 195
E4 l Actuation of low pressure sensor 197
E5 l Compressor motor lock 199
E9 l Malfunction of moving part of electronic expansion valve (Y1E,
Y3E)
201
F3 l Abnormal discharge pipe temperature 203
F6 l Refrigerant overcharged 204
HJ l Malfunction of water system 206
J3 l Malfunction of discharge pipe thermistor (R3T)
(loose connection, disconnection, short circuit, failure)
208
J4 l Malfunction of heat exchanger gas pipe thermistor (R4T) 209
J5 l Malfunction of thermistor (R2T) for suction pipe (loose connection,
disconnection, short circuit, failure)
210
J7 l Malfunction of liquid pipe thermistor (R6T) 211
J9 l Malfunction of subcooling heat exchanger outlet thermistor (R5T) 212
JA l Malfunction of discharge pipe pressure sensor 213
JC l Malfunction of suction pipe pressure sensor 214
L0 l Inverter system error
L4 l Malfunction of inverter radiating fin temperature rise 215
L5 l Inverter compressor abnormal 216
L6 l Compressor motor coil grounding or short circuit
L8 l Inverter current abnormal 217
L9 l Inverter start up error 218
LA l Malfunction of power unit
LC l Malfunction of transmission between inverter and control PC
board
219
Outside Unit P1 l Inverter over-ripple protection 221
P4 l Malfunction of inverter radiating fin temperature sensor 222