Daikin EHYKOMB33AA2 [119/136] Technical data

Daikin EHYKOMB33AA2 [119/136] Technical data
15 Technical data
Installer reference guide
119
EVLQ05+08CAV3 + EHYHBH05AA + EHYHBH/X08AA +
EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1A – 2016.02
Heating only type Reversible
type
Indoor units EHYHBH05 EHYHBH08 EHYHBX08
Connected to outdoor unit EVLQ05CAV3 EVLQ08CAV3 EVLQ08CAV3
Refrigerant circuit
Gas side Ø15.9mm
Liquid side Ø6.35mm
Operation range
(5)
Outdoor temperature Space heating –25~25°C
Space cooling 10~43°C
Water temperature Space heating 25~55°C
Space cooling 5~22°C
(1) With air purge and bottom side water connection, unit height is 1075mm.
(2) DB/WB7°C/6°C – leaving water condenser 35°C (DT=5°C), boiler bypassed.
(3) DB/WB7°C/6°C – leaving water condenser 45°C (DT=5°C), boiler bypassed.
(4) Boiler bypassed.
(5) For operation range of *HYHB* and *HYKOMB33AA, see operation range drawing.
(6) For manometer, refer to boiler specifications.
(7) Ambient temperature 35°C – leaving water evaporator 7°C (DT=5°C), boiler bypassed.
(8) Ambient temperature 35°C – leaving water evaporator 18°C (DT=5°C), boiler bypassed.
(*) Excluded from scope of PED due to article 1, item 3.6 of 97/23/EC.
Electrical specifications
EHYHBH05 + EHYHBH08 + EHYHBX08
Voltage range
Minimum 207V
Maximum 253V
Wiring connections
Communication cable to outdoor unit Quantity of wires 4G
Type of wires 1.5mm
2
User interface Quantity of wires 2
Type of wires 0.75mm
2
~1.25mm
2
(maximum length 500m)
Preferential kWh rate power supply Quantity of wires Power: 2
Signal: 2
Type of wires Power: 6.3A
(1)
Signal: 0.75mm
2
~1.25mm
2
(maximum length
50m)
Electricity meter Quantity of wires 2
Type of wires Minimum 0.75mm
2
(5VDC pulse detection)
Gas meter Quantity of wires 2
Type of wires Minimum 0.75mm
2
(5VDC pulse detection)
Domestic hot water pump Quantity of wires 2
Type of wires Minimum 0.75mm
2
(2A in rush, 1A
continuous)
For connection with R5T Quantity of wires Note
(2)
Type of wires
For connection with R6T Quantity of wires 2
Type of wires Minimum 0.75mm
2
For connection with A3P Quantity of wires Note
(4)
Type of wires Note
(1)
and
Note
(3)
For connection with M2S Quantity of wires 2
Type of wires Note
(1)
and
Note
(3)
For connection with M3S Quantity of wires 3
Type of wires Note
(1)
and
Note
(3)
For connection with optional FWXV (demand input
and output)
Quantity of wires 4
Type of wires 100mA, minimum 0.75mm
2
(1) Select diameter and type according to national and local regulations.
(2) Wire included in option EKEPHT3H.
(3) Voltage: 230V / maximum current: 100mA / minimum 0.75mm
2
(4) Depends on thermostat type, refer to the installation manual