Daikin Altherma hybrid heat pump
4P355634-1A – 2016.02
as electricity. The primary energy factor for natural gas is 1.
Assuming an average electricity production efficiency (including
transportation losses) of 40%, the primary energy factor for
electricity equals 2.5 (=1/0.40). The primary energy factor allows you
to compare 2 different energy sources. In this case, the primary
energy use of the heat pump is compared to the natural gas use of
the gas boiler.
# Code Description
N/A [7‑03] Compares the primary energy use of the
heat pump with that of the boiler.
Range: 0~6, step: 0.1 (default: 2.5)
INFORMATION
The primary energy factor can always be set, but is
only used in case the savings mode is set to
Ecological.
To set electricity price values, do NOT use overview
settings. Set them in the menu structure instead
([7.4.5.1], [7.4.5.2], and [7.4.5.3]). For more information
on how to set the energy prices, see the operation
manual and the user reference guide.
Space heating/cooling control
The basic required settings in order to configure the space heating/
cooling of your system are described in this chapter. The weather-
dependent installer settings define the parameters for the weather-
dependent operation of the unit. When weather-dependent operation
is active, the water temperature is determined automatically
depending on the outdoor temperature. Low outdoor temperatures
will result in warmer water and vice versa. During weather-
dependent operation, the user has the possibility to shift up or down
the target water temperature by a maximum of 10°C.
See the user reference guide and/or operation manual for more
details about this function.
Leaving water temperature: Main zone
# Code Description
[A.3.1.1.1] N/A LWT setpoint mode:
Fixed: The desired leaving water
temperature is:
NOT weather-dependent (i.e. does
NOT depend on the outdoor
ambient temperature)
fixed in time (i.e., NOT scheduled)
Weather dep. (default): The desired
leaving water temperature is:
weather-dependent (i.e. depends
on the outdoor ambient
temperature)
fixed in time (i.e., NOT scheduled)
continued >>
# Code Description
[A.3.1.1.1] N/A << continuation
Fixed/scheduled: The desired leaving
water temperature is:
NOT weather-dependent (i.e.,
does NOT depend on the outdoor
ambient temperature)
according a schedule. The
scheduled actions consists of
desired shift actions, either preset
or custom.
Remark: This value can only be
set in leaving water temperature
control.
WD/scheduled: The desired leaving
water temperature is:
weather-dependent (i.e., does
depend on the outdoor ambient
temperature)
according a schedule. The
scheduled actions consists of
desired leaving water
temperatures either preset or
custom
Remark: This value can only be
set in leaving water temperature
control.
# Code Description
[7.7.1.1] [1‑00]
[1‑01]
[1‑02]
[1‑03]
Set weather-dependent heating:
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]
T
t
: Target leaving water temperature
(main)
T
a
: Outdoor temperature
continued >>