Daikin EHYKOMB33AA2 [12/136] Identification label gas boiler

Daikin EHYHBH08AAV32 [12/136] Identification label gas boiler
5 About the units and options
Installer reference guide
12
EVLQ05+08CAV3 + EHYHBH05AA + EHYHBH/X08AA +
EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1A – 2016.02
Code Description
HBH HBH=Hydrobox heating only
HBX=Hydrobox heating and cooling
05 Capacity class
AA Model series
V3 Power supply
5.2.3 Identification label: gas boiler
Location
Model identification
No:
Anno:
Type:
NOx classe:
PIN:
G.C.:
Qnw(net)
PMW
kW
kW
kW
bar
Qn (net)
Pn
PMS
bar
°C
0063
2013
Tmax
Condensing boiler
b
i
j
a
c
d
e
f
k
l
m
n
o
p
q
r
g
h
a Model
b Serial number
c Production year
d Appliance type
e NOx class
f PIN number: notified body reference
g Destination country
h Gas type
i Gas supply pressure (mbar)
j Appliance category
k Domestic hot water heat output (kW)
l Maximum domestic hot water pressure (bar)
m Heat output (space heating) (kW)
n Nominal power (kW)
o Maximum space heating pressure (bar)
p Maximum flow temperature (°C)
q Electrical supply
r GCN gas council number
5.3 Combining units and options
5.3.1 Possible options for the outdoor unit
Drain pan (EKDP008CA)
The drain pan is required to gather the drain from the outdoor unit.
The drain pan kit consists of:
Drain pan
Installation brackets
For installation instructions, see the installation manual of the drain
pan.
Drain pan heater (EKDPH008CA)
The drain pan heater is required to avoid freezing-up of the drain
pan.
It is recommended to install this option in colder regions with
possible low ambient temperatures or heavy snowfall.
For installation instructions, see the installation manual of the drain
pan heater.
INFORMATION
In case the drain pan heater is used, the jumper JP_DP on
the service PCB on the outdoor unit MUST be cut.
After cutting the jumper, you MUST reset the outdoor unit
to activate this function.
U-beams (EKFT008CA)
The U-beams are installation brackets on which the outdoor unit can
be installed.
It is recommended to install this option in colder regions with
possible low ambient temperatures or heavy snowfall.
For installation instructions, see the installation manual of the
outdoor unit.
5.3.2 Possible options for the indoor unit
User interface (EKRUCBL*)
The user interface and a possible additional user interface are
available as an option.
The additional user interface can be connected:
To have both:
control close to the indoor unit,
room thermostat functionality in the principal space to be
heated.
To have an interface containing other languages.
Following user interfaces are available:
EKRUCBL1 contains following languages: German, French,
Dutch, Italian.
EKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
EKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
EKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
EKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.

Содержание

Скачать