8 Configuration
Installer reference guide
69
EVLQ05+08CAV3 + EHYHBH05AA + EHYHBH/X08AA +
EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1A – 2016.02
# Code Description
[A.6.1] [3‑00] Is the auto restart function of the unit
allowed?
0: No
1 (default): Yes
Preferential kWh rate power supply
# Code Description
[A.2.1.6] [D‑01] Connection to a preferential kWh rate
power supply:
0 (default): The outdoor unit is
connected to a normal power supply.
1: The outdoor unit is connected to a
preferential kWh rate power supply.
When the preferential kWh rate signal
is sent by the electricity company, the
contact will open and the unit will go in
forced off mode. When the signal is
released again, the voltage-free
contact will close and the unit will
restart operation. Therefore, always
enable the auto restart function.
2: The outdoor unit is connected to a
preferential kWh rate power supply.
When the preferential kWh rate signal
is sent by the electricity company, the
contact will close and the unit will go in
forced off mode. When the signal is
released again, the voltage-free
contact will open and the unit will
restart operation. Therefore, always
enable the auto restart function.
Power saving function
Defines whether the outdoor unit power supply can be interrupted
(internally by indoor unit control) during stand-still conditions (no
space heating/cooling by the heat pump). The final decision to allow
power interruption of the outdoor unit during standstill depends on
the ambient temperature, compressor conditions and minimum
internal timers.
To enable the power saving function setting, [E‑08] needs to be
enabled on the user interface in combination with the removal of the
power saving connector at the outdoor unit.
NOTICE
The power saving connector at the outdoor unit shall only
be removed when the main power supply to the application
is switched OFF.
1 2 3
# Code Description
N/A [E‑08] Power saving function for outdoor unit:
0: Disabled
1 (default): Enabled
Power consumption control
Pwr consumpt. control
# Code Description
[A.6.3.1] [4-08] Mode:
0 (No limitation)(default): Disabled.
1 (Continuous): Enabled: You can
set one power limitation value (in A
or kW) to which the system power
consumption will be limited for all the
time.
2 (Digital inputs): Enabled: You can
set up to four different power
limitation values (in A or kW) to
which the system power
consumption will be limited when the
corresponding digital input asks.
[A.6.3.2] [4-09] Type:
0 (Current): The limitation values are
set in A.
1 (Power)(default): The limitation
values are set in kW.
[A.6.3.3] [5-05] Value: Only applicable in case of full
time power limitation mode.
0A~50A, step: 1A (default: 50A)
[A.6.3.4] [5-09] Value: Only applicable in case of full
time power limitation mode.
0kW~20kW, step: 0.5kW (default:
20kW)
Amp. limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on current values.
[A.6.3.5.1] [5-05] Limit DI1
0A~50A, step: 1A (default: 50A)
[A.6.3.5.2] [5-06] Limit DI2
0A~50A, step: 1A (default: 50A)