Daikin EKOMB28AAV1H [49/432] A label pump led flashes red

Daikin EKOMB28AAV1H [49/432] A label pump led flashes red
Daikin Europe NV 49
side.
8.3.8 CH installation stays warm unwanted
Possible causes:
Solution/cause:
Room thermostat/weather dependent regulation
faulty or short circuited.
Yes Æ
Check the wiring.
Check OpenTherm and On/off connection of the unit.
Replace the thermostat.
Replace the weather-dependent regulation.
No È
CH installation is heated due to Tap comfort.
The service display regularly shows code 7.
Yes Æ
Unwanted circulation in the CH circuit due to thermosiphon effect or second pump in
the CH circuit. Install a check valve in case of thermosiphon effect or a two-way
valve in case of a second pump.
No È
8.3.9 A-label pump LED flashes intermittently red/green
Possible causes:
Solution:
Too high or too low mains voltage.
Yes Æ
Check the mains voltage.
No È
Pump temperature is too high.
Yes Æ
Check the water and ambient temperature.
8.3.10 A-label pump LED flashes red
Possible causes:
Solution:
Pump stopped.
Yes Æ
Reset the pump by switching off the unit by pressing the on/off button for at least 20
seconds (attention: if the pump has been set to continuous, the pump can only
be reset by pulling the plug from the socket).
Replace the pump.