Daikin RZQ71C7V1B [145/314] Troubleshooting

Daikin RZQ71C7V1B [145/314] Troubleshooting
Troubleshooting Based on Equipment Condition SiBE28-804
134 Troubleshooting
Troubleshooting
Measure the temperature of
suction air and supply air.
Temperature difference
= Suction air temp. –
Supply air temp.
Does
indoor unit air flow rate
down?
Is
the level of high
pressure higher than
normal level?
Temperature
difference for cooling should
be between 8 and
18˚C.
Does
any frost
generate around inlet
port of indoor unit heat
exchanger or outlet port
of expansion
valve?
Possible causes as follows
* Incorrect selection of model
* Affection of direct sun
Gas shortage possibly
generates trouble.
* Clogged air filter
* Soiled heat exchanger
* Malfunction of fan motor
(Refer error code “A6”.)
Possible causes as follows
* Refrigerant overcharge
* Air in refrigerant system
* Soiled heat exchanger
* Short circuit of supply air
* Disturbing item in air flow
* Malfunction of fan motor of
outdoor unit
(Refer error code “E7”.)
Does the
heat load increase
after installation
of the unit?
Is
the operation
current less than specified
level?
Possible causes as follows
* Insufficient compression
of compressor
* Insufficient circulation
of refrigerant
* Faulty expansion valve
Normal.
Additional unit installation
should be considered.
After vacuum drying,
charge correct amount of
refrigerant.
Check each item.
Check each item.
Check each section.
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
(S1994)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.