Daikin RZQ71C7V1B [201/314] Troubleshooting

Daikin RZQ71C7V1B [201/314] Troubleshooting
Troubleshooting by Remote Controller Display / LED Display SiBE28-804
190 Troubleshooting
3: For thermistor temperature and
resistance characteristics, Refer
to Check 4,5 on P228~229.
4: For voltage characteristics of the
pressure sensor, see the right
figure.
0.5
0.5
0
0.5
1.0
2.0
3.0
3.5
1.5
2.5
0.5 1.5 2.5 3.50123
Output voltage V (VDC)
PH
(MPa)
PH
P = 1.38V
0.69
P : Detected pressure (MPa)
V : Output voltage
Detected pressure
Does
the malfunction
code "E9"
recur?
YES
NO
Restart operation.
Actually, it is in wet operation.
Refer to
(P236~239) to
eliminate the causes of wet operation.
1: Electronic expansion valve and connector No.
2: Electronic expansion valve connector and
coil resistance criteria
Check 13,14,15
It is believed that factors
(noise, etc.,) other than failure
caused the malfunction.
Replace the outdoor PC
board (A1P).
RZQ71~140C7, RZQS71~140C7 X21A
A
1
2
3
4
5
6
(White)
(Yellow)
(Orange)
(Blue)
(Brown)
(Red)
RZQ71C7V1B
RZQS71·100C7V1B
COM (+) (Gray)
1
2
3
4
5
6
(Orange)
(Red)
(Yellow)
(Black)
(Gray)
(White)
RZQ100~140C7V1B
RZQS125·140C7V1B
Measurement
spot
1 - 6
3 - 6
2 - 5
4 - 5
Criteria
40 ~ 50
40 ~ 50
40 ~ 50
40 ~ 50
Measurement
spot
1 - 5
2 - 5
3 - 5
4 - 5
Criteria
40 ~ 50
40 ~ 50
40 ~ 50
40 ~ 50