Troubleshooting by Remote Controller Display / LED Display SiBE28-804
202 Troubleshooting
Troubleshooting
Is
instantaneous voltage
drop generated?
Is the
compressor coil
disconnected or is the
insulation
defective?
Turn the main power supply
off, and then disconnect the
connection between the
compressor and inverter.
Continuity check in the
power transistor (IGBT)
Is the continuity
normal?
Is the stop valve open?
Check the
installation conditions.
Check the power
supply voltage.
Is the
inverter
output voltage
generated approximately
at the same increasing speed
for each phase after
turning on again?
() (U-V, V-W,
W-U)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Open the stop valve.
Replace the compressor.
Correct the power supply.
Compressor inspection
Inspect according to the
diagnosis procedure for
abnormal noise, vibration,
operating status, etc. of the
compressor.
RZQ71C7V1B,RZQS71·100C7V1B
RZQ100~140,RZQS125·140C7V1B
Instantaneous overcurrent
detection value
32.0A
51.7A
YES
NO
NO
YES
YES
NO
Approximate value
NO
YES
NO
YES
* When operating compressor
with compressor output line
disconnected, the compressor
stops due to malfunction after
elapsed time of 5 seconds.
Therefore, check the voltage
increase for 5 seconds.
Check 11
RZQ71C7, RZQS71·100C7:
Replace the outdoor PC
board (A2P).
RZQ100~140C7,
RZQS125·140C7:
Replace the inverter PC
board (A2P).
RZQ71C7, RZQS71·100C7:
Replace the outdoor PC
board (A2P).
RZQ100~140C7,
RZQS125·140C7:
Replace the inverter PC
board (A2P).
(P235)