Daikin RZQ71C7V1B [200/314] Troubleshooting

Daikin RZQ71C7V1B [200/314] Troubleshooting
SiBE28-804 Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 189
Troubleshooting
YES
YES
NO
NO
NO
YES
YES
NO
YES
NO
YES
NO
Turn OFF the power supply
once and then turn it ON again.
Does the
malfunction code
"E9" recur?
Is
the coil
resistance of the
electronic expansion
valve normal?
(2)
Is
the electronic
expansion valve
connector properly
connected to the outdoor
PC board?
(1)
Is
the temperature
sensor of each thermistor
(suction pipe, discharge pipe, intermediate
heat exchanger and heat exchanger
distribution pipe thermistors)
mounted properly?
Are
the characteristics
of each thermistor normal?
(3)
Are
the pressure sensor
characteristics normal?
(4)
Connect properly.
Replace the coil
of the electronic
expansion valve.
Mount properly.
Replace the
abnormal thermistor.
Replace the
pressure sensor.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.