Daikin RZQ71C7V1B [176/314] Troubleshooting

Daikin RZQ71C7V1B [176/314] Troubleshooting
SiBE28-804 Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 165
Troubleshooting
Is the limit
switch's transfer
connector correctly
connected?
Are
the connectors
correctly connected
to X29A and X14A
on the PC
board?
Does the swing
flap motor swing?
Does
continuity/
no continuity
reverse?
220-240 VAC?
Connect correctly.
Turn the power supply
off once and back on,
and check whether the
swing flap motor swings
when the power supply
is turned back on.
Turn the power supply
off once and back on,
and measure the output
voltage of connector
X29A when the power
supply is turned back on.
Disconnect X14A, turn
the power supply off once
and back on, and check if
the limit switch has
continuity when the power
supply is turned back on.
NO
Connect correctly.
NO
Replace the indoor
unit PC board.
Replace the swing
flap motor.
NO
NO
NO
YES
YES
YES
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES

Содержание