SiBE28-804 Method of Operating Remote Controller
Remote Controller 27
3.2 Maintenance Mode Setting
3.2.1 Service Data Confirmation
Procedure
1. Enter the field set mode.
Continue to push the inspection / test operation button for a minimum of 4 seconds.
2. Enter the service mode.
After having entered the field set mode, continue to push the inspection / test operation
button for a minimum of 4 seconds.
3. Select the mode No.
Set the desired mode No. with the up/down temperature setting button.
4. Select the unit No.
Select the indoor unit No. set with the TIME MODE START/STOP button.
5. Select the necessary settings for each mode. (Modes 40 or 41)
6. Select the desired malfunction hysteresis of sensor data display with or button.
(In case of wireless remote controller, use or button.)
Each data displays (Refer below display)
7. Return to the normal operation mode.
Press the inspection / test operation button one time.
Table
5
4
3
1, 2, 7
Mode
No.
Function Content and Operation Method Example of Remote Controller Display
40 Malfunction
Hysteresis
You can change the history
with the programming time up-
down button.
41 Sensor Data
Display
Select the display sensor with
the programming time up-
down button
Display sensor
00 Remote control sensor
01 Suction
02 Heat exchange