SiBE28-804 Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 161
Troubleshooting
Note: If "A3" is detected by a PC board which is not mounted with X15A, the PC board is defective.
Begin
Is the
unit a
cassette or
built-in
Is a
drain pump
connected to the
indoor unit
PCB?
Does the
drain pump work after
restarting operation?
Is the
drain water level
abnormally
high?
Is
the float
switch connected
to X15A?
Does
"A3" appear on
the remote controller
display?
220-240
VAC?
Is there
continuity?
Is the
optional
drain raising
mechanism
Is
the short
circuit connector
connected to X15A on
the indoor unit
PCB?
Connect the
Short-circuit
connector.
Connect the
Short-circuit
connector.
Set to
"emergency"
and check
the voltage
of X25A.
Replace the
drain pump.
Remove the float switch
from X15A, short-circuit
X15A, and restart operation.
Replace indoor
unit PC board.
There is a
malfunction of
the drain system.
Replace
float switch.
Replace the
indoor unit PCB.
Connect
float
switch
Connect
the drain
pump.
Replace
indoor unit
PC board.
Check the continuity of the
short-circuit connector.
NO
YES
YES
YES
YES YES
YES
YES
YES
YES
NO NO
YES
NO
NO
NO
NO NO
NO
NO
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.