Daikin FH35BZV1 [213/397] Condensation avoidance control

Daikin FUYP100BV1 [213/397] Condensation avoidance control
ESiEN02–01A Overview of the cooling mode functions
Part 2 Functional Description 2–35
3
2
4
5
1
2.8 Condensation Avoidance Control
Applicable units FHYP
Operating modes Regardless of whether the thermostat is ON or OFF, the condensation avoidance control can function
in the following operating modes:
Cooling (automatic), or
Dry keep.
Method To avoid condensation on the swing flap, the condensation avoidance control is activated:
Stage Description
1 The fan operates in cooling mode with the blade in downward position (set on the remote
control).
2 After 30 min, the blade moves to a horizontal position. However, the remote control still
shows the downward position.
3 After 1 h operation in horizontal position, the blade moves back to its downward position
for 30 min.
4 The unit operation is reset by:
Changing the operating mode into “heating” or “fan”, or
Changing the air flow direction, or
Turning the unit operation ON or OFF.