Daikin FH35BZV1 [247/397] Outdoor safety device high pressure switch

Daikin RYP100B7W1 [247/397] Outdoor safety device high pressure switch
ESiEN02–01A Troubleshooting
Part 3 Troubleshooting 3–19
33
4
5
1
1.13 Outdoor Safety Device: High-Pressure Switch
High-pressure
switch
The table below describes the high-pressure switch.
Applicable
outdoor unit
Wiring
symbol
Location
safety
Settings Type
Abnormal Reset Reset
RP71B7V1
S1PH
Discharge
pipe
> 33 bar < 25.5 bar
Automatic
RYP71B7V1
RP71B7W1
RYP71B7W1
RP71B7T1
RP100B7V1
RYP100B7V1
RP100B7W1
RYP100B7W1
RP100B7T1
RP125B7W1
RYP125B7W1
RP125B7T1
RP200B7W1
> 32.5 bar < 25 bar
RYP200B7W1
RP250B7W1
RYP250B7W1

Содержание