Daikin FH35BZV1 [265/397] Esien02 01a error codes outdoor units

Daikin RP71B7W1 [265/397] Esien02 01a error codes outdoor units
ESiEN02–01A Error Codes: Outdoor Units
Part 3 Troubleshooting 3–37
33
4
5
1
The fan is turning
clockwise
To troubleshoot, proceed as follows:
Excessive
compressor current
To troubleshoot, proceed as follows:
The fan is turning
clockwise.
Check condensator
connection.
Refer to: fan motor
condensator connection.
Is the
connection
correct?
Replace fan
motor.
Correct the connection.
Refer to: fan motor
condensator connection.
No
Ye s
Is there
a suitable
power supply? (Voltage,
lack of phase, etc.)
Provide suitable
power supply.
No
Is the current higher
than the setting of the
overcurrent relay?
Replace
overcurrent
device.
Ye s
Ye s
No
The compressor current is
excessive.
Check power
supply
Replace
compressor.