5.7 Outdoor Unit: Checking the Expansion Valve
Checking To check the electronic expansion valve, proceed as follows:
Step Action
1 Check if the expansion valve connector is correctly inserted in the X24A of PCB 1.
2 Compare the expansion valve unit with the number of the connector to make sure it is cor-
rectly connected.
3 Switch the power OFF.
4 Switch the power ON to check whether the expansion valve is producing a clicking sound.
5 Check the coil current: Open circuit < normal < short circuit
6 Check the clicking sound again.
If... Then...
The expansion valve has no
clicking sound
Disconnect the valve connector without the
clicking sound and proceed to step 5.
The table below contains the reference resistance values.
Grey Black Yellow Red Orange
Grey
40-50 40-50 40-50 40-50
Black
40-50 80-100 80-100 80-100
Yellow
40-50 80-100 80-100 80-100
Red
40-50 80-100 80-100 80-100
Orange
40-50 80-100 80-100 80-100
If... Then...
There is a clicking sound The expansion valve works properly.
There is no clicking sound Replace the expansion valve unit.
There is still no clicking sound Replace outdoor PCB 1.