Daikin FH35BZV1 [245/397] Outdoor safety device overcurrent relay compressor

Daikin RP125B7T1 [245/397] Outdoor safety device overcurrent relay compressor
ESiEN02–01A Troubleshooting
Part 3 Troubleshooting 3–17
33
4
5
1
1.11 Outdoor Safety Device: Overcurrent Relay Compressor
Overcurrent relay
compressor
The table below describes the overcurrent relay of the compressor.
Applicable
outdoor unit
Wiring symbol Location safety
Settings Type
Abnormal Reset
RP71B7V1
F1C Switch box
> 22.0 A (±10 %)
Automatic
RYP71B7V1
RP71B7W1
> 10.0 A (±10 %)
RYP71B7W1
RP71B7T1 > 15.0 A (±10 %)
RP100B7V1
> 33.0 A (±10 %)
RYP100B7V1
RP100B7W1
> 10.0 A (±10 %)
RYP100B7W1
RP100B7T1 > 22.0 A (±10 %)
RP125B7T1 > 24.0 A (±10 %)
RP125B7W1
> 13.0 A (±10 %)
RYP125B7T1
RP200B7W1
> 16.0 A (±10 %)
RYP200B7W1
RP250B7W1
> 20.0 A (±10 %)
RYP250B7W1

Содержание

Скачать