8 | Configuration
Installer reference guide
117
CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
# Code Description
[7.7.2.1] [0‑00]
[0‑01]
[0‑02]
[0‑03]
Set weather-dependent heating:
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
T
t
: Target leaving water temperature
(additional)
T
a
: Outdoor temperature
continued >>
# Code Description
[7.7.2.1] [0‑00]
[0‑01]
[0‑02]
[0‑03]
<< continuation
[0‑03]: Low outdoor ambient temperature.
40°C~+5°C (default: –10°C).
[0‑02]: High outdoor ambient temperature.
10°C~25°C (default: 15°C).
[0‑01]: Desired leaving water temperature
when the outdoor temperature equals or
drops below the low ambient temperature.
[9‑05]°C~[9‑06]°C (default: 60°C).
Note: This value should be higher than [0-00]
as for low outdoor temperatures warmer
water is required.
[0‑00]: Desired leaving water temperature
when the outdoor temperature equals or
rises above the high ambient temperature.
[9‑05]°C~min(45, [9‑06])°C (default: 35°C).
Note: This value should be lower than [0-01]
as for high outdoor temperatures less warm
water is required.
Pump control: Flow target
The hybrid module is designed to operate with a fixed flow. This means that the
pump is controlled to work at a flow target set by the installer. The installer can set
the flow target for:
heat pump only operation,
hybrid operation,
gas boiler only operation.