7 | Installation
Installer reference guide
95
CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
b NOT allowed.
7.12.6 Flue pipe position
See the local and national regulations.
Especially for UK:
Only use flue products approved by the boiler manufacturer, which can be bought
from the supplier of your boiler.
See "5.3Combining units and options"[427].
P
S
C
B
A
M
R
D
J
Q
G
A
Q
Q
N
P
T2 T2
T2
T1
H
T
I
K
L
F
F
N
E
Terminal position Minimum distance
(mm)
A Directly below an open able window or other
opening (e.g. air brick)
300
B Below gutters, soil pipes or drain pipes 75
C Below eaves 200
D Below balconies or car front roofs
E From vertical drain pipes and soil pipe 150
F From internal or external corners 300
G Above ground, roof or balcony level
H From a surface facing a terminal 600