ABB ACH550-02-645A-4 [270/454] Parameter listing and descriptions

ABB ACH550-02-645A-4 [270/454] Parameter listing and descriptions
266 Parameter listing and descriptions
ACH550-02 User's Manual
A parameter can be connected to only one timer.
Code Description Range
3601 TIMERS ENABLE -6…7
Selects the source for the timer enable signal.
0 =
NOT SEL – Timed functions are disabled.
1 =
DI1 – Defines digital input DI1 as the timed function enable signal.
• The digital input must be activated for timed functions enable.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the timed function
enable signal.
7 =
ACTIVE – Timed functions are enabled.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the timed function
enable signal.
• This digital input must be de-activated for timed function enable.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as the timed function enable signal.
3602 START TIME 1 00:00:00…23:59:58
Defines the daily start time.
The time can be changed in steps of 2 seconds.
If parameter value is 07:00:00, the timer will be activated at 7 a.m.
The figure shows multiple periods on different weekdays.
TIMER 1
3626 TIMER 1 SRC
TIMER 2
3627 TIMER 2 SRC
1001 EXT1 COMMANDS
1002 EXT2 COMMANDS
1102 EXT1/EXT2 SEL
1201 CONST SPEED SEL
1401 RELAY OUTPUT 1…1403 RELAY OUTPUT 3
1410 RELAY OUTPUT 4…1412 RELAY OUTPUT 6
4027
PID 1 PARAM SET
4228 ACTIVATE
8126 TIMED AUTOCHANGE
Mon Tue Wed Thu Fri Sat Sun
09:00:00
10:30:00
12:00:00
13:00:00
15:00:00
17:00:00
20:30:00

Содержание

Похожие устройства

Скачать