ABB ACH550-02-645A-4 [350/454] Parameter listing and descriptions

ABB ACH550-02-645A-4 [350/454] Parameter listing and descriptions
346 Parameter listing and descriptions
ACH550-02 User's Manual
HVAC
default Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
123456
29 MAINTE-
COOLING
FAN TRIG
2901 0.0 kh 0.0 kh 0.0 kh 0.0 kh 0.0 kh 0.0 kh
NANCE
TRIG
COOLING
FAN ACT
2902 0.0 kh 0.0 kh 0.0 kh 0.0 kh 0.0 kh 0.0 kh
REVOLUTION
TRIG
2903 0 Mrev 0 Mrev 0 Mrev 0 Mrev 0 Mrev 0 Mrev
REVOLUTION
ACT
2904 0 Mrev 0 Mrev 0 Mrev 0 Mrev 0 Mrev 0 Mrev
RUN TIME
TRIG
2905 0.0 kh 0.0 kh 0.0 kh 0.0 kh 0.0 kh 0.0 kh
RUN TIME
ACT
2906 0.0 kh 0.0 kh 0.0 kh 0.0 kh 0.0 kh 0.0 kh
USER MWH
TRIG
2907 0.0 MWh 0.0 MWh 0.0 MWh 0.0 MWh 0.0 MWh 0.0 MWh
USER MWH
ACT
2908 0.0 MWh 0.0 MWh 0.0 MWh 0.0 MWh 0.0 MWh 0.0 MWh
30 FAULT
AI<MIN
FUNCTION
3001 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
FUNCTIONS
PANEL COMM
ERR
3002 FAULT FAULT FAULT FAULT FAULT FAULT
EXTERNAL
FAULT 1
3003 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
EXTERNAL
FAULT 2
3004 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
MOT THERM
PROT
3005 FAULT FAULT FAULT FAULT FAULT FAULT
MOT THERM
TIME
3006 1050 s 1050 s 1050 s 1050 s 1050 s 1050 s
MOT LOAD
CURVE
3007 100% 100% 100% 100% 100% 100%
ZERO SPEED
LOAD
3008 70% 70% 70% 70% 70% 70%
BREAK POINT
FREQ
3009 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz 35 Hz
STALL
FUNCTION
3010 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
STALL
FREQUENCY
3011 20.0 Hz 20.0 Hz 20.0 Hz 20.0 Hz 20.0 Hz 20.0 Hz
STALL TIME 3012 20 s 20 s 20 s 20 s 20 s 20 s
EARTH FAULT 3017 ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE
COMM FAULT
FUNC
3018 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
COMM FAULT
TIME
3019 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
AI1 FAULT
LIMIT
3021 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
AI2 FAULT
LIMIT
3022 0.0% 0.0% 0.0% 0.0% 0.0% 0.0%
WIRING
FAULT
3023 ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE
CB TEMP
FAULT
3024 ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE