Technical data 397
ACH550-02 User’s Manual
Note 1: The ratings apply in ambient temperatures up to 40 °C
(104 °F).
Derating
The load capacity (current and power) decreases if the
installation site altitude exceeds 1000 m (3300 ft), or if the
ambient temperature exceeds 40 °C (104 °F).
Temperature derating
In the temperature range +40 °C…50 °C (+104 °F…122 °F), the
rated output current has to be decreased 1% for every 1 °C
(1.8 °F) above 40 °C (+104 °F). The output current is calculated
by multiplying the current given in the rating table by the derating
factor.
Example. If the ambient temperature is 50 °C (+122 °F), the
derating factor is 100% - 1%/°C = 90% or 0.90.
The output current is then 0.90 ·I
2N
.
Altitude derating
In altitudes from 1000…4000 m (3300…13,200 ft) above sea
level, the derating is 1% for every 100 m (330 ft). If the
installation site is higher than 2000 m (6600 ft) above sea level,
please contact your local ABB distributor or office for further
information (see page 421).