66 Installing the drive
ACH550-02 User’s Manual
Check installation
Check
The ambient operating conditions are allowed. See
Ratings on page 395 and Ambient conditions on
page 413.
The unit is fixed properly on floor and a vertical
non-flammable wall.
The cooling air will flow freely.
The motor and the driven equipment are ready for
start. See Motor compatibility on page 23 and Motor
connection on page 404.
Varistors have been disconnected if the drive is
connected to an IT (unearthed) system or corner-
earthed TN system. See IT systems and corner-
earthed TN systems on page 45.
The capacitors are reformed if stored over one year
(refer to Guide for Capacitor Reforming in ACS50,
ACS55, ACS150, ACS310, ACS350, ACS355,
ACS550 and ACH550 (3AFE68735190 [English]).
The drive is properly earthed.
The mains (input power) voltage matches the drive
nominal input voltage.
The mains (input power) connections at U1, V1 and
W1 and their tightening torques are OK.
Appropriate mains (input power) fuses and discon-
nector are installed. See Disconnecting device
(means) on page 30 and Input power (mains)
cables, fuses and circuit breakers on page 398.
The motor connections at U2, V2 and W2 and their
tightening torques are OK.
The motor cable is routed away from other cables.
Setting of the fan voltage transformer. See Settings
of the cooling fan transformer on page 64.