Protection Control Si34-803_B
151 Function
4. Protection Control
4.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
[In cooling operation]
In case of multi-outdoor-unit system, each outdoor unit performs this control individually in
the following sequence.
[In heating operation]
In case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
High pressure not limited
Pc>3.43MPa
High pressure standby
INV upper limit
rps
= max
Current step maintained
Pc>3.43MPa
Pc>3.64MPa
Pc<3.24MPa
After 10 sec.
After 10 sec.
After 15 sec.
Pc>3.55MPa
STD compressor
standby
Pc: High pressure sensor detection
value for each outdoor unit
When occurring 3 times within
30 min., HPS is activated without high
pressure standby, thus outputting the
malfunction code “E3.
INV upper limit frequency:
3-step down from current
compressor rps
(Slave unit: 3-step down as well)
INV upper limit
frequency
:
1-step up from current
compressor frequency
(Slave unit: Same as above)
High pressure not limited
Pc>3.10
MPa
System load down 1 steps
Current step maintained
Pc>3.10
MPa
EV1 opening adjustment
(Reducing low pressure to make
high pressure lower.)
Pc>3.49
MPa
High pressure standby
Pc>3.64
MPa
Pc<2.9
MPa
Pc: High pressure sensor detection
value for master unit
When occurring 3 times within
30 min., HPS is activated without high
pressure standby, thus outputting the
malfunction code “E3.
After 10 sec.
Pc<3.0MPa
Pc<2.52MPa
After
60 sec.
INV upper limit
rps: 1-step up