Daikin RXYQ36PAYL [332/452] Reverse phase open phase

Daikin RXYQ30PAYL [332/452] Reverse phase open phase
Troubleshooting by Indication on the Remote Controller Si34-803_B
321 Troubleshooting
3.45
U1
Reverse Phase, Open Phase
Remote
Controller
Display
U1
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
The phase of each phase are detected by reverse phase detection circuit and right phase or
reverse phase are judged.
Malfunction
Decision
Conditions
When a significant phase difference is made between phases.
Supposed
Causes
Power supply reverse phase
Power supply open phase
Defect of outdoor unit PCB (A1P)
Troubleshooting
Operation
is normal if one
place of power supply
line phase is
replaced.
Fix the open phase. Requires
inspection of field power supply
section.
Reverse phase.
Counter measure of the problem is
completed by phase replacement.
Replace the outdoor unit PCB
(A1P).
YES
YES
NO
NO
There
is an open phase
at the power supply
terminal section (X1M)
of the outdoor
unit.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.