Daikin RXYQ36PAYL [303/452] Troubleshooting

Daikin RXYQ36PAYL [303/452] Troubleshooting
Si34-803_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 292
Troubleshooting
(Orange) 1
Measuring points
1 - 6
2 - 6
3 - 6
4 - 6
(Red) 2
(Yellow) 3
(Black) 4
5
(Gray) 6
Make measurement of resistance
between the connector pins, and
then make sure the resistance
falls in the range of 40 to 50.
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Return to normal?
Turn power supply off, and
turn power supply on again.
Electronic
expansion valve is
connected to X21A and
X23A of outdoor unit
PCB (A1P).
Normal
when coil
check (1) of the
electronic expansion
valve coil is
checked.
The connecting
cable is short-circuited or
disconnected.
Replace the connecting cable.
Replace the outdoor unit PCB
(A1P).
NO
NO
*X26A only for RXYQ5M
NO
NO
Replace the electronic expansion
valve coil.
External factor other than
malfunction (for example, noise
etc.).
After connecting, turn the power
off and then back on again.
YES
YES
YES