Si34-803_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 290
Troubleshooting
Note: Refer to check 1 and 2 on P.356.
Resistance
of the U, V, and W
phases of the fan motor
has got imbalanced or short
circuits have been established
among the U, V,
and W
phases.
Check 1
Check for the fan motor
connector (Power supply cable)
Check 2
Check for the fan motor
connector (Signal cable)
NO
NO
YES
Turn ON the power supply.
NO
Has a
short circuit been
established between
the fan motor signal cables Vcc
and GND, and UVW
and GND,
respectively?
YES
The LED
(HAP) on the
compressor inverter PCB
is blinking, but the LED (HAP)
on the fan inverter
PCB is not
blinking.
YES
Replace the outdoor unit fan
motor.
Replace the outdoor unit fan
motor.
Replace the fan inverter
PCB.
Replace the outdoor unit fan
motor.
A