Daikin RXYQ36PAYL [246/452] Setting of vacuuming mode

Daikin RXYQ24PAYL [246/452] Setting of vacuuming mode
Field Setting Si34-803_B
235 Test Operation
3.2.5 Setting of Vacuuming Mode
In order to perform vacuuming operation at site, fully open the expansion valves of indoor and
outdoor units and turn on some solenoid valves.
[Operating procedure]
c
With Setting Mode 2 while the unit stops, set “Refrigerant recovery / Vacuuming mode” to
ON. The expansion valves of indoor and outdoor units fully open and some of solenoid
valves open.
(H2P blinks to indicate the test operation, and the remote controller displays "Test
Operation" and "Under centralized control", thus prohibiting operation.)
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
d
Use the vacuum pump to perform vacuuming operation.
e
Press Mode button “BS1” once and reset “Setting Mode 2”.
3.2.6 Check Operation Detail
Unit stopping
Press the TEST button for 5 seconds.
10 sec to 10 minutes
LED display (H1P~H7P) (
k :ON h :OFF l :BLINK)
hhkhhhh
hlhhhhk
Pressure equalizing
Step 1
20 sec to 2 minutes
10 minutes
5 minutes
hlhhhkh
Cooling start controlStep 2
hlhhhkk
hlhkhhk
hlhkhkh
Stability waiting operationStep 3
Pump down residual operation
Step 9
5 minutes
Standby for restarting
Completion
Step 10
Stop valve close check
Wrong wiring check
Correct Refrigerant charge check
Piping length check
hlhhkhh
hlhhkhk
hlhhkkh
hlhhkkk
hlhkhhh
Judgement function
Step4~8
CHECK OPERATION FUNCTION
(Press the MODE button BS1 once and set to SETTING MODE 1 (H1P: OFF))