Daikin RXYQ36PAYL [416/452] Outdoor unit 60hz

Daikin RXYQ30PAYL [416/452] Outdoor unit 60hz
List of Electrical and Functional Parts Si34-803_B
405 Appendix
3.2 Outdoor Unit - 60Hz
3.2.1 RXYQ5 / 8PAYL, PTL
Item Name Symbol
Model
RXYQ5PAYL RXYQ8PAYL
Compressor
Inverter
Type
M1C
JT1GCVDKYR@SB
OC protection
device
14.7A
STD 1
Type
M2C
OC protection
device
STD 2
Type
M3C
OC protection
device
Fan motor
OC protection
device
M1F 1.15A 3A
Electronic expansion valve (Main) Y1E Fully closed: 0pls Fully open: 480pls
Electronic expansion valve (Subcooling) Y2E
Fully closed: 0pls
Fully open: 480pls
Pressure
protection
High pressure
switch
For M1C S1PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M2C S2PH
For M3C S3PH
Low pressure sensor S1NPL OFF: 0.07MPa
Temperature
protection
Discharge gas temperature
protection
(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature
protection
(Radiator fin thermistor)
R1T OFF: 93°C
Others Fuse
For main PCB
A1P 250V, 15A
A2P 250V, 3A (PTL : 250V, 15A)
For Noise filter
PCB
F1U 250V AC 6.3A Class B
+0
0.12

Содержание

Скачать