Daikin RXYQ36PAYL [336/452] Outdoor unit check operation is not executed

Daikin RXYQ30PAYL [336/452] Outdoor unit check operation is not executed
Troubleshooting by Indication on the Remote Controller Si34-803_B
325 Troubleshooting
3.47
U3
Outdoor Unit: Check Operation is not Executed
Remote
Controller
Display
U3
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Check operation is executed or not
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
Check operation is not executed.
Troubleshooting
Performs the check operation
again and completes the check
operation.
When a leakage detection
function is needed, normal
operation of charging refrigerant
must be completed. And then,
start once again and complete a
check operation.
Has the
check operation
performed on outdoor
unit PCB?
Press and hold BS4 on the
outdoor master PCB for 5
seconds or more, or turn ON the
local setting mode 2-3 to conduct
a check operation.
NO
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.