Daikin RXYQ36PAYL [352/452] Troubleshooting

Daikin RXYQ30PAYL [352/452] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si34-803_B
341 Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
YES
After fixing incorrect wiring,
push and hold the RESET
button on the master outdoor
unit PCB for 5 seconds.
Normal
NO
Is
electricity
being introduce for
the first time after
installation or after an indoor
or outdoor unit PCB
has been
replaced?
Is
indoor - outdoor and
outdoor - outdoor unit
transmission wiring
normal?
Push and hold the RESET
button on the outdoor unit
PCB for 5 seconds
YES
NO
Normal
NO
Does a
malfunction occur?
Mount the DIII-NET extension
adaptor.
YES
Disconnect
the outdoor-outdoor
unit transmission
wiring to create the one-
system status, and then
check whether or not
the system is
normal.
NO
Does
a "UH" malfunction occur
for all indoor units in
the system?
YES
NO
Does
a malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor
and outdoor
units?
YES
Replace the indoor unit PCB.
Replace the outdoor unit PCB
(A1P).
The unit will not run for up to
12 minutes.

Содержание

Скачать