Daikin RXYQ36PAYL [216/452] Outdoor air processing unit field setting remote controller

Daikin RXYQ36PAYL [216/452] Outdoor air processing unit field setting remote controller
Field Setting Si34-803_B
205 Test Operation
3.1.7 Outdoor Air Processing Unit - Field Setting (Remote Controller)
Note) Bold face in indicates the factory setting.
Mode
No.
First
Code
No.
Setting
contents
Second Code No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
10
(20)
0 Stain of filter2500hr 1250hr —————————————
3
Filtering
time
cumulation
Display
No
display
—————————————
12
(22)
1
External
ON/OFF
input
Forced
stop
ON-OFF
control
—————————————
5
Power
failure
automatic
reset
Not
equipped
Equipped—————————————
14
(24)
3
Discharge
temperature
(cooling)
13°C 14 15 16 17 18 19 20 21 22 23 24 25 25 25
4
Discharge
temperature
(heating)
18°C 19 20 21 22 23 24 25 26 27 28 29 30 30 30